B10B2-00
B10B2-00-A/C COOL DOWN TEST PERFORMANCE
For a complete wiring diagram, refer to the wiring information Electrical Diagrams.
Theory of Operation
The A/C Heater Controller has software to enable it to perform an A/C Cool Down Test by a command using a scan tool. This test checks for evaporator temperature drop over a predetermined time. If the test fails, this DTC will set. However, certain test conditions are required to perform this test. Failure to run this test within those parameters can result in failure of the test.
- When Monitored:
With ever an A/C Cool down Test is performed.
- Set Condition:
This DTC is set whenever the A/C Cool down Test is performed and the desired temperature drop is not achieved by the system. The DTC will go to stored after a successful A/C Cool down Test.
Always perform the HVAC Pre-Diagnostic Troubleshooting procedure before proceeding. HVAC Pre-Diagnostic Troubleshooting Procedure.
CONDITIONS FOR A/C COOLDOWN TEST
1. The following condition must be met before running the A/C Cool down test.
- No Powertrain Control Module (PCM) DTCs present.
- No Communication DTCs present.
- Condenser cooling fan working properly.
- No active HVAC evaporator temperature sensor, sun sensor, recirculation, mode, or blend door actuator DTCs present.
- The refrigerant system must be fully charged.
- The blower motor must operate correctly in all speeds.
- The evaporator temperature must be above 12.7° C (55° F).
- The A/C compressor must be turned off.
- Blower must be on high.
Are all of the above conditions met before running the A/C Cool down Test?
Yes
- Go to the Service Information for additional Cool down Test related diagnostic information and testing procedures and repair as necessary. NOTE: Run the Cool down Test again after any repairs are performed.
- If the Cool down Test passes, testing is complete.
No
- Run the A/C Cool down test again with the above test conditions.