Test Point 3
Test point 3
Interior temperature sensor
Open circuit
Short to ground
DTC 22
Diagnosis conditions
No control module fault stored.
No fault on the supply voltage (5 Volt).
Outside temperature higher than - 40 °C.
Open circuit
1. Pull off connector A on the heating/air conditioning control.
2. Connect ohmmeter to connector A 10 and A 12.
Display: approx. 3 kOhms at 23 °C
NOTE: The wires to the interior temperature sensor are routed via two additional plug connections on the heating/air conditioning control.
3. Pull off connector on the interior temperature sensor.
4. Connect ohmmeter to connector A 10 and interior sensor connector pin 5.
Display: < 5 Ohms
5. Connect ohmmeter to connector A 12 and interior sensor connector pin 4.
Display: < 5 Ohms
6. Connect voltmeter to connector A 10 and ground.
Switch on ignition.
Display: 0 Volt
If approx. 5 Volt is displayed, check the wiring for pinching and chafing.
Short to ground
1. Pull off connector A on the heating/air conditioning control.
2. Connect ohmmeter to connector A 7 and ground.
Display: Infinity Ohms
If 0 - 5 Ohms is displayed, check the wiring for pinching and chafing.