Starting From Cold
Starting From Cold In AUTO Working Mode^ Air distribution damper, cold start positions:
Blended air temperature: damper:
below +35°C (95°F) DEFROST position
+35 - +50°C (95 - 122°F) off DEFROST on HEAT position
above +50°C (122°F) normal operation
^ Ventilation fan, speed when starting from cold:
Blended air temperature: current about:
below +35 °C (95°F) 4.5 A
+35 - +5O °C (95 - 122°F) 4.5 - 6.4 A
+50 - +55°C (122 - 131°F) 6.4 - 12 A
^ As soon as the value calculated by the ACC unit for blended-air temperature drops below +80 °C (176°F), but no less than 1 minute after starting, a switch over to normal operation takes place for both the air distribution damper and fan speed.