Accumulator HVAC: Service and Repair
Removing
- Discharge A/C refrigerant system Service and Repair
- Remove front bumper as complete unit. [1][2]Procedures
- Remove bolts -A-.
- Disconnect refrigerant line -B-. Tightening torque: 40 Nm (30 ft. lb)
- Remove nuts -D-.
- Remove accumulator together with bracket.
- Disconnect refrigerant line -B-.
Tightening torque: 40 Nm (30 ft. lb)
NOTE: Replace both O-rings (17.2 mm x 1.8 mm).
- Seal off all open connections.
Installing
Install refrigerant lines free of stress and make sure there is sufficient clearance between lines and other components.
- When installing the accumulator in the bracket, always install insulation -F-.
- Install spring -C- so it is positioned against marking on refrigerant hose and engaged on bracket.