Temperature Setting Trimmer
WITH LEFT AND RIGHT VENTILATION TEMPERATURE SEPARATELY CONTROL SYSTEM : Temperature Setting TrimmerDESCRIPTION
The trimmer compensates for differences in range of ±3 °C (±6 °F) between temperature setting (displayed digitally) and temperature felt by customer.
Operating procedures for this trimmer are as per the following:
1. Begin self-diagnosis STEP-5 mode. Refer to HAC-63, "WITH LEFT AND RIGHT VENTILATION TEMPERATURE SEPARATELY CONTROL SYSTEM : Diagnosis Description". With Left and Right Ventilation Temperature Separately Control System
2. Press fan (UP: +) switch to set system in auxiliary mode.
3. Display shows "61" in auxiliary mechanism. It takes approximately 3 secondsto enable setting operation.
4. Turn temperature control dial (driver side) as desired. Temperature will change at a rate of 0.5 °C (1.0 °F) each time a dial is turned.
CAUTION: A decimal point is not indicated on the display.
When battery cable is disconnected or battery voltage is below 10 V, trimmer operation is canceled. Temperature set becomes that of initial condition, i.e. 0 °C (0 °F).